Harmonics compensator

Power
10÷100 kVA
Primary
400 V
Secondary
400 V + N

 

Harmonics filtering and electromagnetic interferences reduction due to the galvanic isolation between input and output.

Applications

Improve the power factor increasing the active power available in the network, SAI´S, transforming and generator sets.

Reduction of the neutral current and neutral earth voltage
Reduction of voltage and current distortion

  • TAC3: Three-phase mains with single-phase loads that generate homopolar harmonics: 3º-9º-15º (Computers, fluorescent and discharge lamps, motor starter...) Eliminates the overload in the neutral conductor and the high neutral - earth voltage
  • TAC5: Three-phase mains with three-phase loads that generate harmonics 5º-7º-17º (motor starter, rectifiers, motor regulator DC,...)
    Output filtering load 50%

Technical features

Frequency 50/60 Hz
Rated temperature 30º C
Thermal isolation Class F
Winding Class H-180º C
Degree of protection IP23
Yield > 95%

  • Absence of electronic components and capacitors.

 

Connecting system

  • Accesible and protected connections