Passive harmonic filters for VFD IP20

Passive harmonic filter especially designed for 6 pulses power converters such as frequency converters, variable speed drives for motors, three phase rectifiers, battery chargers, HVAC systems, etc. Protection degree IP20.

Specifications

Specifications

Motor rating
4 ÷ 220 kW
(5,5 ÷ 300 CV)
Nominal current 9 ÷ 408 A
Nominal voltage
3 x 400 V ± 20 V
Frequency 50 Hz
Harmonic order filtering
3º, 5º, 7º, 11º, 13º
Load distortion 75-100%
≈ 5 % THD-I
Load distortion 50-75%
≈ 6 % THD-I
Load distortion< 50%
≈ 8 % THD-I
Load 100 % power factor
≥ 0,99
                        * with load > 40%
≥ 0,9
Ambient Temp.
30 ºC
Protection degree
IP-20
Cooling Natural air
Marked CE
Standard IEC/UNE-EN 60076-6
IEC/UNE-EN 61006-6

Downloads

Contact us for further information

Contact us for further information

Please read the Terms of Service and Privacy Policy and confirm you agree with them before sending the form.

Electrical diagram

 

Dimensions

 
Referencias 1 a 1 de 1
  SPF004 SPF005 SPF007 SPF011 SPF015 SPF018 SPF022 SPF030 SPF037 SPF045 SPF055 SPF075 SPF090 SPF110 SPF132 SPF150 SPF160 SPF185 SPF200 SPF220
Request offer Request Request Request Request Request Request Request Request Request Request Request Request Request Request Request Request Request Request Request Request
Power (kW) 4 5,5 7,5 11 15 18,5 22 30 37 45 55 75 90 110 132 150 160 185 200 220
Power (CV) 5,5 7,5 10 15 20 25 30 40 50 60 75 100 125 150 180 205 220 270 270 300
Current (A) 9 12 16 23 30 37 43 58 72 86 104 140 168 204 245 278 296 341 369 406
Losses (W) 165 190 225 310 350 405 450 565 610 670 720 975 1145 1345 1435 1505 1610 1660 1835 1835
IP 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
Phases Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase
Use Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD
Ambient temperature 30ºC 30ºC 30ºC 30ºC 30ºC 30ºC 30ºC 30ºC 30ºC 30ºC 30ºC 30ºC 30ºC 30ºC 30ºC 30ºC 30ºC 30ºC 30ºC 30ºC
Electric shock protection Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I
Converter voltage 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V 380V ÷ 420V
A 290 290 290 330 330 330 330 410 410 410 410 490 490 570 570 570 570 570 570 570
B 250 250 250 315 315 315 315 390 390 390 390 410 410 470 470 470 470 470 470 470
C 510 510 510 610 610 610 610 670 670 670 670 1275 1275 1520 1520 1520 1520 1520 1520 1520
Weight (Kg) 21,0 24,6 27,2 34,3 40,7 50,4 56,0 66,2 84,5 94,4 105 129 147 193 222 235 269 298 320 356
Type 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2