Single-phase control transformer (IP20) CSE0040-3
  • Data (SEC)
  • Data (PRI)
  • Dimensions
  • Wiring
  • Protection
POWER (VA)
Nominal 40
Snapshot 80
INTENSITY - SECONDARY (A)
115V 0.348
230V 0.174
POWER (VA)
Nominal 40
Snapshot 80
INTENSITY - PRIMARY (A)
230V 0.174
400V 0.1
460V
POWER (VA) 40
DIMENSIONS (mm)
A 82
B 90
C 92
D 58
E 79
Ø 5,5x12
WEIGHT (kg) 1.1
TYPE I
POWER (VA) 40
MIN. PRIMARY CONDUCTOR SIZE (mm2 )
230V 0.5
400V 0.5
460V
MIN. SECONDARY CONDUCTOR SIZE (mm2)
12V 0,75
24V 0.5
48V 0.5
115V 0.5
230V 0.5
POWER (VA) 40
PRIMARY (A) PROTECTIONS (T / D / aM)
230 V 0,200
400 V 0,125
460 V
SECONDARY PROTECTIONS (A) (F / C / gG)
12V 3.15
24V 1.6
48V 0.8
115V 0.315
230V 0.16