Single-phase control transformer (IP20) CSE4000-3
  • Data (SEC)
  • Data (PRI)
  • Dimensions
  • Wiring
  • Protection
POWER (VA)
Nominal 4000
Snapshot 12500
INTENSITY - SECONDARY (A)
115V 34.783
230V 17.391
POWER (VA)
Nominal 4000
Snapshot 12500
INTENSITY - PRIMARY (A)
230V 17.391
400V 10
460V 8.696
POWER (VA) 4000
DIMENSIONS (mm)
A 240
B 255
C 235
D 205
E 235
Ø 9x18
WEIGHT (kg) 53
TYPE IV
POWER (VA) 4000
MIN. PRIMARY CONDUCTOR SIZE (mm2 )
230V 2.5
400V 1
460V 1
MIN. SECONDARY CONDUCTOR SIZE (mm2)
12V
24V
48V
115V 6
230V 2.5
POWER (VA) 4000
PRIMARY (A) PROTECTIONS (T / D / aM)
230 V 20
400 V 12
460 V 10
SECONDARY PROTECTIONS (A) (F / C / gG)
12V
24V
48V
115V 32
230V 16