Three-phase isolation transformer TTS010
  • Data
  • Dimensions
  • Wiring and protection
IP IP00
POWER (kVA) 10
INTENSITY (A)
Primary 14.451
Secondary 14.451
Ucc (%) 4.2
PERFORMANCE η (%) 95
POWER (kVA) 10
DIMENSIONS (mm)
A 360
B 225
C 355
D 320
E 150
Ø 11
WEIGHT (kg) 62
TYPE I
POWER (kVA) 10
TTC - Cable Grommets
Max. Ø (mm) PG-38
Quantity 2
TTP - Presses
Max. Ø (mm) PG-29
Quantity 2
PROTECTIONS PRIMARY (A)
(D/aM) 32
PROTECTIONS SECONDARY (A)
(C/gG) 14