Three-phase high power transformer TTHC1250
  • Data
  • Dimensions
  • Wiring and protection
IP IP21
POWER (kVA) 1250
TENSIÓN (V)
Primary 400
Secondary 400
INTENSITY (A)
Primary 1804
Secondary 1804
Ucc (%) 4.2
PERFORMANCE η (%) 98.9
POWER (kVA) 1250
DIMENSIONS (mm)
A 2100
B 1300
C 2400
D 550
E 1150
Ø 16
WEIGHT (kg) 3600
TYPE VI
POWER (kVA) 1250
PROTECTIONS PRIMARY (A)
(D/aM) 4000*
PROTECTIONS SECONDARY (A)
(C/gG) 1600