Three phase input line reactor for VFD

Three-phase input line reactor specially designed for power converters such as variable speed drives, UPS systems, rectifiers, soft-starters and other types of non-linear loads. Protection degree IP-00 with varnish finish.

Specifications

Specifications

 
Motor rating 0,75 ÷ 220 kW (1 ÷ 300 CV)
Nominal current
2 ÷ 500 A
Nominal voltage
380 V - 500 V
Inductive impedance
± 3,5 %
Frequency  50/60 Hz
Distortion 75÷100% load
≈ 35 % THD-I
Distortion 50÷75% load
≈ 45 % THD-I
Distortion < 50% load
≈ 60 % THD-I
Admissible overload Permanent 1,07 x I.nom
Transitory 1,5 x I.nom
Ambient temp. 50 ºC @ I.nom
Insulation class
F (155ºC)
Protection degree
IP-00
Cooling Natural air
Safety class Class I
Test voltage
4 kV
Marked CE
Standard IEC/UNE-EN 60076-6

 

 

Downloads

Contact us for further information

Contact us for further information

Please read the Terms of Service and Privacy Policy and confirm you agree with them before sending the form.

Electrical diagram

 

Dimensions

 
Referencias 1 a 1 de 1
  ILT002 ILT004 ILT006 ILT008 ILT010 ILT015 ILT020 ILT025 ILT030 ILT040 ILT050 ILT060 ILT080 ILT100 ILT125 ILT150 ILT200 ILT250 ILT300 ILT400 ILT500
Request offer Request Request Request Request Request Request Request Request Request Request Request Request Request Request Request Request Request Request Request Request Request
Current (A) 2 4 6 8 10 15 20 25 30 40 50 60 80 100 125 150 200 250 300 400 500
L (mH) 12,812 6,406 4,271 3,203 2,562 1,708 1,281 1,025 0,854 0,641 0,512 0,427 0,320 0,256 0,205 0,171 0,128 0,102 0,085 0,064 0,051
Input Voltage(V) 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V 380V ÷ 500V
IP 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
Phases Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase Three-phase
Use Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD Line for VFD
Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Ambient temperature 50ºC 50ºC 50ºC 50ºC 50ºC 50ºC 50ºC 50ºC 50ºC 50ºC 50ºC 50ºC 50ºC 50ºC 50ºC 50ºC 50ºC 50ºC 50ºC 50ºC 50ºC
Thermic class F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC) F (155ºC)
Electric shock protection Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I Classe I
Test voltage 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV 4 kV
A 120 120 120 120 150 150 150 190 190 190 240 240 240 240 300 300 300 300 300 360 360
B 75 75 84 84 73 98 98 108 113 123 131 131 151 166 163 183 173 183 193 210 210
C 122 122 122 122 149 164 164 205 205 205 209 209 209 209 252 252 302 302 302 363 363
D 94 94 94 94 100 100 100 140 140 140 200 200 200 200 200 200 200 200 200 320 320
E 47 47 57 57 47 62 62 72 77 87 90 90 110 125 100 120 110 120 130 130 130
ø 6,5 6,5 6,5 6,5 7 7 7 7 7 7 7 7 7 7 11 11 11 11 11 11 11
Weight (Kg) 1,1 1,2 1,7 1,8 2,3 3,7 3,9 5,4 6,2 7,6 9,6 10,1 14,7 18,4 21,1 28 28,8 34,4 39,3 52,4 55,7
Type I I I I I I I II II II II II II II III III III III III III III